Configuration
3.6 Serial interface
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
43
3.6
Serial interface
3.6.1
Advanced options
3.6.1.1
Dedicated line
Settings dedicated line
Settings serial interface
Interface standard
Standard of the serial interface: RS232 / RS485
Select the following value:
RS232
When a modem with an RS-232 interface is connected to the interface of the TIM
RS485
When a modem with an RS-485 interface is connected
With parallel connection of several modems to the interface of the TIM (star-shaped
network)
RS-485 termination
Enable this option when connecting a terminating resistor for the RS-485 bus when a
star-shaped network is connected.
Operating mode
Only configurable with: TIM 3V-IE DNP3 / TIM 4R-IE DNP3
The operating mode of the interface specifies the mode of the data transfer. Range of
values:
Interrupt (block) - for the send and receive direction
DMA - for the send and receive direction.
Interrupt (individual characters) - only for the receive direction
A maximum of one of two serial interfaces of a module may be operated in DMA mode.
Max. number of spontaneous frames
Only configurable with: TIM 3V-IE DNP3 / TIM 4R-IE DNP3