Functions and requirements
1.5 Performance data and configuration limits
Configuration - DNP3
16 Configuration Manual, 11/2018, C79000-G8976-C508-01
1.5
Performance data and configuration limits
1.5.1
TIM 1531 IRC
Connection resources
Telecontrol connections
The number of connections or communications partners is limited for the two interface
types and every individual interface.
Note that redundant connection paths of a connection between two partners require two
connection resources on each partner.
Max. number of connections: 128
Distribution over 4 interfaces can take place in any way (max. 128 per interface).
E-mail
A connection to send e-mails can be established during runtime.
S7 connections
Max. 4 connection resources for PG/OP connections (see below)
PG/OP connections
4 connection resources for connections to the engineering station or HMI devices
(included in the configuration limits of the S7 connections, see above)
PG routing
Max. 4 connections at the same time
Online functions
See PG/OP connections
HTTP/HTTPS
Max. 2 connections per Ethernet interface
Number of data points for the data point configuration
The maximum number of configurable data points is 3000.
Message memory: Send buffer / SD card
The TIM has a frame memory (send buffer) for the values of data points configured as an
event.
The send buffer has the following maximum size (number of events):
250000
The size of the frame memory is divided equally among all configured communications
partners.