Configuration
3.5 Ethernet interface
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
41
3.5.2
Advanced options
3.5.2.1
TCP connection monitoring
Ethernet interface > Advanced options > TCP connection monitoring
The settings of the two parameters at the Ethernet interface govern TCP connections via this
interface.
You can adapt the parameters in the properties of the telecontrol connections for each
connection segment.
TCP connection monitoring time
Function: If no data traffic takes place within the TCP connection monitoring time, the
module sends a keepalive frame to the communication partner.
With the setting 0 (zero), the function is disabled.
Default setting: 180 s
Permitted range
TIM 1531 IRC
1...65535 s
CP 1243-1 / CP 1243-8 IRC / TIM 3V-IE DNP3 / TIM 4R-IE DNP3
0...65535 s
CP 1542SP-1 IRC
0...32767 s
TCP keepalive monitoring time
After sending a keepalive frame, the module expects a response from the communication
partner within the keepalive monitoring time. If the module does not receive a response
within the configured time, it closes the connection.
With the setting 0 (zero), the function is disabled.
Default setting: 10 s
Permitted range
TIM 1531 IRC
1...65535 s
CP 1243-1 / CP 1243-8 IRC
0...65535 s
TIM 3V-IE DNP3 / TIM 4R-IE DNP3
1...255 s
CP 1542SP-1 IRC
0...32767 s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TeleControl DNP3 and is the answer not in the manual?

Siemens SIMATIC TeleControl DNP3 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TeleControl DNP3
CategoryControl Unit
LanguageEnglish

Related product manuals