Functions and requirements
1.5 Performance data and configuration limits
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
19
Size of the message memory for events
TIM 3V-IE DNP3: 64 000 events
TIM 4R-IE DNP3: 200 000 events
Number of S7 connections via Ethernet
In addition to the DNP3 connections, the number of possible S7 connections via the Ethernet
interface is as follows:
TIM 4R-IE DNP3
Number in total: Max. 5,
of which:
2 configurable S7 connections
2 PG connections
1 OP connection
TIM 3V-IE DNP3
Number in total: Max. 3,
of which:
2 PG connections
1 OP connection
No S7 connections can be established via the serial interface.
Number of MODBUS slaves per station
The maximum number of MODBUS slaves that can be connected to the serial interface of a
TIM depends on the configured interface standard:
RS-232: Maximum of 1 MODBUS slave
RS-485: Maximum of 8 MODBUS slaves
1.5.3
CP 1243-8 IRC
Number of CMs/CPs per station
In each S7-1200 station, up to three CMs/CPs can be plugged in and configured, of which a
maximum of one CP 1243-8 IRC.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TeleControl DNP3 and is the answer not in the manual?

Siemens SIMATIC TeleControl DNP3 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TeleControl DNP3
CategoryControl Unit
LanguageEnglish

Related product manuals