Configuration
3.20 Configuring data points
Configuration - DNP3
118 Configuration Manual, 11/2018, C79000-G8976-C508-01
Threshold value trigger
Function
If the process value deviates by the amount of the threshold value, the process value is
saved.
Two methods are used to calculate the threshold value deviation:
Absolute method
With binary and counter values as well as with analog values with configured mean value
generation, the absolute method is used to calculate the threshold value deviation.
Integrative method
With analog values without configured mean value generation, the integrating method is
used to calculate the threshold value deviation.
In the integrating threshold value calculation, it is not the absolute value of the deviation
of the process value from the last stored value that is evaluated, but rather the integrated
deviation.
Absolute method
There is a check for each binary value to determine whether the current (possibly smoothed)
value is outside the threshold value band. The current threshold value band results from the
last saved value and the amount of the configured threshold value:
Upper limit of the threshold value band: Last saved value + threshold value
Lower limit of the threshold value band: Last saved value - threshold value
As soon as the process value reaches the upper or lower limit of the threshold value band,
the value is saved. The newly saved value serves as the basis for calculating the new
threshold value band.
Integrative method
The integration threshold value calculation works with a cyclic comparison of the integrated
current value with the last stored value. The calculation cycle in which the two values are
compared is 500 milliseconds.
(Note: The calculation cycle must not be confused with the scan cycle of the CPU memory
areas).
The deviations of the current process value are totaled in each calculation cycle. The trigger
is set only when the totaled value reaches the configured value of the threshold value trigger
and a new process value is entered in the send buffer.
The method is explained based on the following example in which a threshold value of 2.0 is
configured.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TeleControl DNP3 and is the answer not in the manual?

Siemens SIMATIC TeleControl DNP3 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TeleControl DNP3
CategoryControl Unit
LanguageEnglish

Related product manuals