Configuration
3.6 Serial interface
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
49
Transmission setting for conditionally spontaneous messages
Transmission criterion
Only configurable with: CP 1243-8 IRC / TIM 3V-IE DNP3 / TIM 4R-IE DNP3
With TIM 1531 IRC, the settings are transferred by the partner; if the send buffer
overflows, the "Degree of filling" setting is used.
Only for interfaces with the Network node type "Station" / "Node station".
The transmission criterion controls connection establishment for the transmission of
conditional spontaneous messages. This reduces the number of connection retries.
Range of values:
Standard conditions
No connection will be established due to the existence of conditionally spontaneous
messages .
Only in the following cases will a connection be established to send conditional
spontaneous messages.
- Threatened overflow of the send buffer
- Connection establishment by the communications partner
Degree of filling
The TIM only establishes a connection when the configured fill level of the send buffer
for conditional spontaneous messages is exceeded.
In the input box, enter the fill level (%) of the send buffer at which when exceeded the
TIM establishes a connection.
Time
The TIM sends conditional spontaneous messages at a configured time of day,
configurable with "Hours" / "Minutes".
Time scheme
The TIM sends the conditional spontaneous messages cyclically at a configurable
interval, configurable with "Hours" / "Minutes".
Time options
Call acceptance delay
Only with CP 1243-8 IRC
Wait time (s) before accepting an incoming call
Due to the wait time acceptance of the call is possible for the TIM when a telephone is
connected to a shared telephone connection to the TIM.
Default setting: 0. Permitted range: 0...30

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TeleControl DNP3 and is the answer not in the manual?

Siemens SIMATIC TeleControl DNP3 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TeleControl DNP3
CategoryControl Unit
LanguageEnglish

Related product manuals