Configuration
3.19 Telecontrol connections
Configuration - DNP3
90 Configuration Manual, 11/2018, C79000-G8976-C508-01
● Two connections to a partner via the same interface of a module are not allowed.
● A connection via an inconsistent network is invalid.
Example of inconsistent networks:
– A subscriber of a connection segment is connected to another telecontrol protocol.
– Connections via nodes that are not configured as node stations.
– Subscriber with incompatible modems
– Incompatible settings of two modems in a connection
– Incompatible settings between modem and network parameters
Interface-specific configuration of the connection segments
Connections between two endpoints can run over multiple subscribers.
A connection segment between two subscribers can be used for multiple connections.
Individual settings can be configured for specific connection segments and the associated
interfaces of the modules. For this reason, the individual connection segments between the
interfaces of two devices are displayed in separate lines in the connection table.
Figure 3-5 "Network data" editor, "Telecontrol > ..." tab
Creating connections and searching for connection paths
Follow these steps to create connections:
1. Click the "Starting point" field in the next free row.
A drop-down list with the available endpoints is displayed.
The first row below the table header is reserved for entering filters; see section
Connection table (Page 92).
2. Select the starting point (CPU) from the table with a double-click.