The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
176 System Manual, 12/2015, C79000-G8976-C253-04
project. The parameter area for the destination subscriber-specific parameters is opened and
the parameters are set for every configured destination subscriber.
The following destination subscriber-specific parameters are available:
Parameters of the DNP3 master station
Name:
DNP3 implementation level
Range of va
l-
ues:
1 ... 5
Default:
3
Explanation:
With the SINAUT configuration software, you can specify the DNP3 impl
e-
mentation level for each
configured DNP3 master station (subscriber type:
other station). Specify the highest conformity level supported by the DNP3
master station.
Values can be assigned in the range from 1 to 5. Based on this information,
the TIM firmware selects the suitable s
tandard variations of the process
data for this master station.
Level 5 that is not specified in the standard corresponds to implementation
level 4 and additionally includes the support of the following objects / data
types (object group/variation):
•
Frozen counter with time of day in 16-bit format (21/6)
•
Counter event with time of day in 16-bit format (22/6)
•
Analog input, floating point, 32-bit format (30/5)
•
Analog input event, floating point with time, 32-bit format (32/7)
•
Analog output status, floating point, 32-bit format (40/3)
•
Analog output, floating point, 32-bit format (41/3)
Name:
Time stamp
Default:
Function activated
Explanation:
When using DNP3, the parameter is always activated. This cannot be dea
c-
tivated.
The parameter assignment is only
practical if the DNP3 master station was
selected as the destination subscriber.
Data read by the local CPU is given a time stamp before it is sent to the de
s-
tination subscriber.
Copying parameters to other destination subscribers
Once the destination subscriber-specific parameters have been set for a destination
subscriber, they can be transferred to other destination subscribers that require the same
parameters. Follow the steps outlined below:
1. Select a destination subscriber for which you have already set the parameters in the list
box.
2. Select "Copy" in the shortcut menu (right mouse button).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TIM 3V-IE DNP3 and is the answer not in the manual?

Siemens SIMATIC TIM 3V-IE DNP3 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TIM 3V-IE DNP3
CategoryControl Unit
LanguageEnglish

Related product manuals