EasyManua.ls Logo

Siemens SIMATIC TIM 3V-IE DNP3 - Meaning of ERRCLS and ERRCOD

Siemens SIMATIC TIM 3V-IE DNP3
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Diagnostics and upkeep
7.3 SINAUT diagnostics and service tool
TIM DNP3
296 System Manual, 12/2015, C79000-G8976-C253-04
Event ID
(hex)
Detailed
event
(hex)
Status message
Meaning / remark
F460 0808 Message queue overflow (outgoing) Meaning in byte 5 of the diagnostics message:
1 = LAN COM
2 = S7 adapter
3 = Modbus adapter
F960 0809 CTS error (incoming)
F860
0809
CTS error (outgoing)
F560 080A UART error (incoming)
F460
080A
UART error (outgoing)
F360 080B Status change of the MODBUS slave
(incoming)
MODBUS slave not accessible
F260 080B Status change of the MODBUS slave
(outgoing)
MODBUS slave accessible
F560 080C Negative S7 acknowledgement re-
ceived (message only incoming)
Byte 6 of the message codes the error class (ERRCLS)
and byte 7 codes the error code (ERRCOD). For the
meaning of ERRCLS and ERRCOD, see Meaning of
ERRCLS and ERRCOD (Page 296).
F560 080D Negative S7 access result received
(message only incoming)
Bytes 6 and 7 of the message code the access result
(hex) with the following meaning:
FF = success
01 = hardware error
02 = temporary lack of resources
03 = object access not permitted
05 = invalid address
06 = type not supported
07 = type inconsistent
0A = object does not exist
0E...EF: Reserved
FE = data unchanged since last access
7.3.6.5
Meaning of ERRCLS and ERRCOD
Meaning of ERRCLS and ERRCOD in messages 0113 and 080C
Table 7- 6 Meaning of ERRCLS and ERRCOD (hex)
ERRCLS
ERRCOD
Meaning
FF 01 The LAN connection via which the frame is to be sent is not established. The message is
deleted.
FF 02 The queue of the LAN connection via which the frame is to be sent has overflowed. The mes-
sage is deleted.

Table of Contents

Related product manuals