The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
225
Name:
MODBUS role
Explanation:
Specifies the MODBUS role for the TIM.
Only the default role "Master" is possible.
"WAN connection" box
Name:
Interface type:
Explanation:
Selection of the interface standard and the
directional dependency of the
interface
Range of va
l-
ues:
TIM 3V-IE DNP3:
RS-232 half duplex
RS-232 duplex
TIM 4R-IE DNP3:
RS-232 half duplex
RS-232 duplex
RS-485 not terminated
(TIM not as bus terminator)
RS-485 terminated
(TIM as bus terminator)
Name:
Transmission speed
Explanation:
Transmission speed on the serial interface [bps]
Range of va
l-
ues:
300, 600, 1200, 2400, 4800, 9600
Name:
Retry factor
Explanation:
This value decides how often a message that has not been acknowledged
positively is repeated before an error is signaled.
Range of va
l-
ues:
0...255
Default:
3
Name:
Send timeout
Explanation:
Time within which the acknowledgement is expected after sending a me
s-
sage [ms].
Range of va
l-
ues:
0 to 86
400 000 ms (= 24 hours)
Default:
3
Name:
RTS/CTS delay time
Explanation:
After setting RTS, a message is only sent after the configured time has
elapsed.
Range of va
l-
ues:
0 to 65535 ms