Installation and commissioning
4.3 Commissioning the TIM
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
71
LED displays during startup
The following table summarizes the startup phases.
Table 4- 3 LED activity on the TIM 3V-IE DNP3 during the various startup phases
Phase
Activity
SF
RUN
STOP
KBus
TxD
RxD
1 Power ON
followed by hardware initialization
On
On
On
On
On
On
2 Loading the operating system from flash
memory
Off
On
On
On
On
On
3
Starting VxWorks operating system
Off
Off
On
On
On
On
4
Loading and starting TIM firmware
Off
Off
Off
On
On
On
5 Initializing flash file system and starting
the start manager
Off Flashes
On
Off Off Off
6
Loading and starting P bus driver
Off
Flashes
On
On
Off
Off
7 Loading and starting subscriber man-
agement (SubA)
Off Flashes
On
Off
On
Off
8
Loading and starting LAN-COM
Off
Flashes
On
On
On
Off
9 Loading and starting subscriber man-
agement (MesA)
Off Flashes
On
Off Off
On
10
Loading and starting time-of-day driver
Off
Flashes
On
On
Off
On
11 Loading and starting the TD7 software of
the TIM (TD7onTIM) on the TIM
Off Flashes
On
Off
On
On
12
Loading and starting WAN driver
Off
Flashes
On
On
On
On
13a
Startup completed without error
Off
On
Off
X
1)
X
1)
X
1)
13b
Startup completed with error
On
Off
On
X
2)
X
2)
X
2)
13c Startup aborted - user parameter assign-
ment missing. Module expects user pa-
rameter assignment
Off Off
On
Flashes Flashes
On
13d Startup aborted -
No firmware loaded
Off Off
On
On
Flashes Flashes
13e Startup aborted - No SDBs and no firm-
ware loaded
Off Off
On
Flashes Flashes Flashes
13f
Default startup completed
Off
Flashes
Flashes
On
On
On
13g Startup aborted due to incorrect firmware
(firmware does not match module type)
On
Flashes Flashes Flashes Flashes Flashes
1) The LEDs KBus, TxD and RxD now operate in normal mode
2) The LEDs KBus, TxD and RxD remain in the phase in which the error occurred

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TIM 3V-IE DNP3 and is the answer not in the manual?

Siemens SIMATIC TIM 3V-IE DNP3 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TIM 3V-IE DNP3
CategoryControl Unit
LanguageEnglish

Related product manuals