EasyManuals Logo

Siemens SIMEAS R User Manual

Siemens SIMEAS R
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #144 background imageLoading...
Page #144 background image
12
12.6 Device Function
144 Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Recorder Size in MB
Size of the physical memory area in Mbytes for each recorder.
Recording Depth
Recording time in days (d) and hours (h) - it is calculated from the recording times, the
number of active channels and the configuration components
Total Memory
Total memory capacity of the parameterized recorders.
Avbl. Memory
Memory that can be allocated freely.
OSCOP P monitors the allocation of memory space.
If the memory capacity is not sufficient for a continuous mean value recorder and the overall
memory capacity of the device has been reached, please proceed as follows:
Reduce the memory capacity of another recorder.
Increase the memory capacity of the continuous mean value recorder by the memory space
that has been deallocated beforehand.
Allocate a memory area of at least 1.5 MByte to each recorder.
For system data 100 MByte are reserved. This has to be considered for the hard disk size.
OSCOP P considers this fact automatically when calculating the available memory.
Note
Changes in the memory allocation will delete all data recordings in the device. No warning is
given during parameterization.
Note
Please note that unchecking a checkbox does not automatically deallocate memory space.

Table of Contents

Other manuals for Siemens SIMEAS R

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMEAS R and is the answer not in the manual?

Siemens SIMEAS R Specifications

General IconGeneral
BrandSiemens
ModelSIMEAS R
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals