16.1 Technical Data of the SIMEAS R-PMU
255Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
16.1.9 Climatic Tests
Cold and dry heat IEC 60068-2-1 and IEC 60068-2-2
Transport and storage -25 °C to +70 °C
During operation -5 °C to +55 °C
Air humidity 95 % without condensation
Humid heat IEC 60068-2-3
Temperature change IEC 60068-2-14
Maximum height above
sea level 2000 m (according to IEC 61010-1)
Note
The only permissible operating temperature range for surface-mounted housings is from
0°C to40°C.