3 System Messages
280 Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
A.3 System Messages
The table below contains all messages that the SIMEAS R-PMU logs in the log file:
Legend:
Type 0: Malfunction
Type 1: Warning / important message
Type 2: Operating message
Log No. Type Class Description Comment
258 1 BOOT Reboot initiated -
260 0 BOOT Fault: Task monitor initiating reboot Hotline
262 1 SYSTEM Create system data OK Reorganization of system internal data,
e. g. after upgrade or update
263 0 SYSTEM Create system data canceled with fault Hotline
265 1 SYSTEM Read system data OK -
266 1 SYSTEM System data missing or wrong, new file
written
Reorganization of system internal data,
e. g. after upgrade
267 1 SYSTEM Write system data OK -
268 1 SYSTEM Shutdown measurement system Possible reasons: Change to service mode,
DAU error or device is being shut down
269 0 SYSTEM Restart due to critical system fault
(deadlock). Fault time:
Hotline
270 0 SYSTEM Restart due to critical system fault
(deadlock). Task:
Hotline
273 1 SYSTEM DAU not plugged Status message
274 0 SYSTEM DAU boot fault Several possible reasons: DAU and CPU
software version do not match, firmware
update recommended; DAU hardware error;
contact hotline if necessary
277 2 SYSTEM Self-monitoring -
278 0 SYSTEM Fault: Cannot start self-monitoring Hotline
279 2 SYSTEM Self-monitoring: New MD5 checksum file
created
Checksum file is created again after each
firmware update
280 0 SYSTEM Self-monitoring fault: Cannot write MD5
checksum file
Hotline
281 0 SYSTEM Self-monitoring fault: Critical checksum fault Flash disk fault; Hotline
282 1 SYSTEM Firmware update -
283 0 SYSTEM Firmware update failed Hotline
284 1 SYSTEM Communication subsystem not started.
Reason:
Hotline
285 1 SYSTEM Measurement system not started. Reason: Possibly an error message after an
upgrade, otherwise firmware or OSCOP P
update recommended; contact hotline if
necessary
286 1 SYSTEM Number of device restarts due to critical
system faults:
For further information on this fault, refer to
detailed log entries.
287 0 SYSTEM Fault writing the restart counter Hotline
288 0 SYSTEM Last restart due to critical system fault Hotline
289 2 SYSTEM Restart information written -
290 2 SYSTEM Fault writing the restart information Hotline

Table of Contents

Other manuals for Siemens SIMEAS R

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMEAS R and is the answer not in the manual?

Siemens SIMEAS R Specifications

General IconGeneral
BrandSiemens
ModelSIMEAS R
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals