16
16.1 Technical Data of the SIMEAS R-PMU
251Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
16.1.7 Electrical Tests
Safety regulation IEC 61010-1; EN 61010-1
Protection class IEC 61140; EN 61140
Degree of protection IEC 60529
Flush-mounted housing:
Equipment: Front IP31
Terminals IP21 (standard terminal)
Terminals IP11 (US terminal)
Housing IP20
Operator protection: IP2x (standard terminal)
IP1x (US terminal)
Surface-mounted housing:
Equipment: Front IP31
Terminals IP21
Housing IP21
Operator protection: IP2x
Clearances and creepage distances IEC 61010-1; EN 61010-1
Overvoltage category III
Pollution degree 2
Insulation tests
Voltage test IEC 61010-1; EN 61010-1
(routine test)
Supply voltage DC 3.1 kV
Voltage/current inputs 3.25 kV, 50 Hz
(VCDAU, VDAU, CDAU)
DC inputs DC 2.0 kV
Binary inputs and 2.2 kV, 50 Hz
messages
Impulse voltage test IEC 60255-5
(type test) 1.2/50
μs; 0.5 J
Supply voltage and 6 kV
voltage/current inputs
(VCDAU, VDAU, CDAU)
DC inputs, binary inputs 4 kV
and messages