16
16.1 Technical Data of the SIMEAS R-PMU
252 Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Electromagnetic compatibility
Electromagnetic HF field
amplitude-modulated IEC 61000-4-3
Test level 3, 10 V/m
80 MHz to 1000 MHz,
80 % amplitude modulation
Electromagnetic HF field
single frequencies IEC 60255-22-3
Test level 3, 10 V/m
Frequencies:
80 MHz ±0.4 MHz
160 MHz ±0.8 MHz
450 MHz ±2.25 MHz
900 MHz ±5 MHz
80 % amplitude modulation
900 MHz ±5 MHz
50 % pulse modulation
Magnetic field with
power system frequency IEC 61000-4-8; EN 61000-4-8
Permanent field
Test level 5, 100 A/m
Electrostatic discharge
IEC 61000-4-2; EN 61000-4-2
Contact discharge
Test level 4, test voltage 8 kV
Air discharge
Test level 4, test voltage 15 kV
High frequency, unsymmetrical
amplitude-modulated IEC 61000-4-6; EN 61000-4-6
Test level 3
Voltage level 10 V
Frequency range 150 kHz to 80 MHz
Fast transients (bursts) IEC 61000-4-4; EN 61000-4-4
Power supply AC/DC Test level 4, test voltage 4 kV,
direct coupling
Signal lines, control and
communications lines, data and Test level 4, test voltage 2 kV,
printer lines coupling, cap. data link
Repetition frequency 5 kHz
System frequency, unsymmetrical IEC 60770
Test level 10 V and
Test level 250 V (customer-specific)
1 MHz HF test IEC 60255-22-1
Power supply, system
and communications lines Direct and differential-mode voltage 2.5 kV
Signal lines, data and
printer lines Common-mode voltage 2.5 kV
Differential-mode voltage 1.0 kV