16
16.1 Technical Data of the SIMEAS R-PMU
242 Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
16.1 Technical Data of the SIMEAS R-PMU
16.1.1 Construction
ZE 8/16
Dimensions (W x H x D) 223 mm x 266 mm x 300 mm
Number of slots 3
Slot 1: CPU
Slot 2: DAU
Slot 3: Power supply unit
ZE 32/64
Dimensions (W x H x D) 445 mm x 266 mm x 300 mm
Number of slots 6
Slot 1: CPU
Slots 2to5: DAU
Slot 6: Power supply unit
16.1.2 Supply Voltage
Low-voltage version
Direct voltage
Nominal direct supply voltage DC 24 V / DC 48 V / DC 60 V
Permissible voltage ranges DC 19.2 V to DC 72 V
High-voltage version
Direct voltage
Nominal direct supply voltage DC 110 V / DC 125 V / DC 220 V / DC 250 V
Permissible voltage ranges DC 88 V to DC 300 V
Alternating voltage (50 Hz / 60 Hz)
Nominal alternating supply voltage AC 115 V / AC 230 V
Permissible voltage ranges AC 92 V to AC 276 V
Frequency range 45 Hz to 65 Hz