2 Error Messages
279Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
A.2 Error Messages
OSCOP P displays the following error messages if the communication to SIMEAS R-PMU is
active:
Message ID Error/Message Comment
800 Unknown command received Firmware or OSCOP update recommended, contact
hotline if necessary
801 Incorrect password or command not
executable
Firmware or OSCOP update recommended, contact
hotline if necessary
802 Command not executed Firmware or OSCOP update recommended, contact
hotline if necessary
803 Command executed with error status Firmware or OSCOP update recommended, contact
hotline if necessary
804 Illegal or invalid command parameter Firmware or OSCOP update recommended, contact
hotline if necessary
805 Command executed on inactive
recorder
Unable to execute command: Recorder not active or
parameterized.
807, 810 -
812
File access error Query table of contents again and check if the record has
been deleted via ring buffer mode, contact hotline if
necessary
808 Directory access error Contact hotline
814 Database query outside time range There are no records/entries for the given interval.
815 Database transmission overwritten
by measure
The requested record of a continuous recorder was
overwritten in ring buffer mode.
818 Error during compilation of system
parameters
Firmware or OSCOP update recommended, contact
hotline if necessary
819 Error during compilation of DAU
parameters
Firmware or OSCOP update recommended, contact
hotline if necessary
820 Error during parameterization, file
does not contain system data
Firmware or OSCOP update recommended, contact
hotline if necessary
821 Parameterization error, slot not
occupied
Firmware or OSCOP update recommended, contact
hotline if necessary
822 Parameter file update error Firmware or OSCOP update recommended, contact
hotline if necessary
823 Error during firmware update Check the communication link, contact hotline if
necessary
824 Error setting system information Firmware or OSCOP update recommended, contact
hotline if necessary
825 Data transmission canceled -
830 Time setting via the PC interface is
not allowed with synchronization type
GPS
Time setting via the PC interface is not allowed with
synchronization type GPS/DCF77.
831 Time setting via the PC interface can
be performed only every 4 hours
Set a cycle time of at least 4 hours for automatic time
setting.
832 V2/V3 command rejected You tried to access the SIMEAS R-PMU with device type
SIMEAS R. Create a device in OSCOP P Parameterize
PC with device type SIMEAS R-PMU. This device type is
available in OSCOP P 6.60.
833 Incorrect password Parameterize the correct password, refer to chapter
12.1. In general, the password may be overwritten in the
first 3 minutes after new start of the device.