16
16.1 Technical Data of the SIMEAS R-PMU
249Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Binary outputs (CPU)
Signal outputs Relay 1: Break contact (NC contact),
permanently allocated to watchdog (live
contact)
Relays 2 to 4 make contact (NO contact),
configurable
Default setting:
Relay 2: Device ready for operation
Relay 3: Recording active
Relay 4: Group alarm
Switching capacity ON 30 W resistive
30 VA inductive / capacitive
Switching capacity OFF 30 W resistive
25 VA inductive / capacitive
50 ms
Switching voltage 250 V
Permissible current 1 A continuous
Flash Disk
Flash Disk interface IDE/ATA-1
Data rate 1.2 MByte/s
Capacity 512 MByte or 1 GByte
File system FAT16

Table of Contents