EasyManuals Logo

Siemens SIMEAS R User Manual

Siemens SIMEAS R
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
6
6.3 Calculating Derived Values
49Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Delta connection: phase-to-phase voltages and currents
With and :
Positive-sequence system:
Negative-sequence system:
a e
j 2Π 3()
=
a
2
e
j 2 Π 3()
=
V
1
V
L12
a
2
V
L23
3
----------------------------------------
=
I
1
1
3
---
I
L1
aI
L2
a
2
I
L3
++()=
V
2
V
L12
aV
L23
3
-------------------------------------
=
I
2
1
3
---
I
L1
a
2
I
L2
aI
L3
++()=
Note
Only the absolute value of the symmetrical components is recorded.
Note
The Continuous RMS-value Recorder (CRR) only records the absolute value of the
symmetrical components.
Triggering is also done using only the absolute value of the symmetrical components.
The PMU transfers the positive-sequence system as complex values!

Table of Contents

Other manuals for Siemens SIMEAS R

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMEAS R and is the answer not in the manual?

Siemens SIMEAS R Specifications

General IconGeneral
BrandSiemens
ModelSIMEAS R
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals