Description of the blocks
4.7 MMRevDhl motor block
SIMOCODE pro PCS 7 Library V9.0
206 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
4.7.8
Issuing maintenance release
The maintenance release is information about a measuring point at which maintenance,
service, or calibration work is to be performed. You can use the signal for the maintenance
release to convey information about release of a measuring point from the OS to the
maintenance station.
You issue the maintenance release in the parameter view via operation of the
MS_RelOp = 1
input parameter (operator control permission "high-value process operation" required). A
maintenance release is then provided via the interconnectable output parameter
MS_Release = 1 for further processing. An Operation message is generated.
4.7.9
Suppressing messages using the MsgLock parameter
The MMRevDhl block supports the standard function message suppression. The function is
executed via the
MsgLock parameter.
With the Feature.Bit25, you determine which messages are suppressed via the
MsgLock = 1
parameter:
All messages on the block
All messages on the block except for process control messages, the message class that
is released by the default setting (e.g. CSF, motor protection, feedback error) and
external messages.
Pending messages are given the "output" status with
MsgLock = 1.
4.7.10
Simulation
Simulation is the manipulation of a signal, independently of the actual source of the signal or
logic that generates this signal.
Simulation can only be activated / deactivated with the operator control permission level for
system authorization via
SimOn =1 if SimLiOp = 0 or from the CFC via SimOnLi=1 if SimLiOp =
1
.
During simulation, the Quality Code(ST_Worst) is set to 16#60. The icons for the Quality
Code are displayed in the block icon and in the overview window of the faceplates.
Simulation is triggered during runtime in the faceplate's parameter view by clicking on the
"Simulation" button.
The simulation is characterized as follows:
Simulation can only be activated / deactivated with the operator control permission level
for system authorization.
The technological functions are not influenced
All process-relevant output signals, such as
Fwd, Rev, FFwd, and FRev are given
"Simulation" status.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals