Description of the blocks
4.2 Diagnostics block MMDiag
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
99
4.2.8
Failure of a PROFIBUS DP station
The PROFIBUS connection error is reported at the BusFlt output of the MMDiag block and
as an alarm in WinCC.
Table 4- 9 Possible reasons for the connection error
Byte 0
Meaning
Reason or remedy
Bit 0 1: DP slave cannot be
accessed by the DP
master.
DP slave cannot be accessed by the DP master.
Is the station address of the DP slave set correctly?
Is the bus connection plug connected?
Is voltage applied to the DP slave?
Is the RS 485 Repeater secured correctly?
Has a reset been performed on the DP slave?
4.2.9
Malfunction when loading the OB
Interrupt OB 85 sets or resets the priority class error GrpErr (malfunction when loading OBs).
Table 4- 10 Events during which OB 85 GrpErr is reset
Fault
Event number
Event class
Error when creating a start event for an OB. This is not
loaded to the CPU.
16#A1, 16#A2 or
16#A3
16#35
Error when the operating system accesses a module.
16#B1, 16#B2
16#39
16#B3 16#39 or 16#38
GrpErr is only triggered once for one execution cycle of the block.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
Protection ClassIP20
Mounting TypeDIN rail mounting
Rated Operational Voltage24 V DC
Rated CurrentUp to 820 A
Protection FunctionsOverload, short-circuit, phase failure, asymmetry, ground fault, motor stall
Operating Temperature Range-25°C to +60°C
Communication ProtocolsPROFIBUS DP, PROFINET, Modbus RTU
Analog OutputsUp to 2
Temperature MonitoringPTC/KTY, RTD (PT100/PT1000)
Digital OutputsRelay outputs, Solid-state outputs
Analog Inputs0/4-20mA, PT100/PT1000

Related product manuals