Page #244 background imageLoading...
Page #244 background image
Parameter
A.3 Block parameter MMOprtn
SIMOCODE pro PCS 7 Library V9.0
244 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
A.3
Block parameter MMOprtn
Input parameters
Table A- 11 Input parameter MMOprtn
Parameter
Data format
Default setting
Meaning
Mode
DWORD
16#8000FFFF
OMODE information of MOD_SWT
RackF STRUCT
Value: BOOL
ST: BYTE
0
16#80
1 = Rack failure information from MMDiag
ModF STRUCT
Value: BOOL
ST: BYTE
0
16#80
1 = Module failure information from
Slv_Typ BOOL FALSE 0 = PROFIBUS
1 = PROFINET
DAddr
INT
0
Diagnostics address of SIMOCODE
LAddr
INT
0
Logical address of SIMOCODE
RdWrEn
BOOL
TRUE
1 = Enable read/write data record
RdDataLi STRUCT
Value: BOOL
ST: BYTE
0
16#80
Input 0->1 = Read data record via Link or SFC
RdDataOp
BOOL
FALSE
1 = Read data from datasets
ModLiOp STRUCT
Value: BOOL
ST: BYTE
0
16#80
Input to Auto/Manual Commands
0 = Manual
1 = Link/Auto
AutModOp
BOOL
FALSE
1 = AUTO mode via operator
ManModOp
BOOL
TRUE
1 = MANUAL mode via OS operator
AutModLi STRUCT
Value: BOOL
ST: BYTE
0
16#80
1 = AUTO mode via Link or SFC
ManModLi STRUCT
Value: BOOL
ST: BYTE
0
16#80
1 = MANUAL mode via Link or SFC
Diag_Sts SMCSTATUS SIMOCODE diagnostics status information from
MMDiag
Diag_Evt SMCEVNT SIMOCODE diagnostics event information from
MMDiag
Diag_Wrn SMCWRNG SIMOCODE diagnostics warning information from
MMDiag
Diag_Trp SMCTRP SIMOCODE diagnostics trip information from
MMDiag

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
Protection ClassIP20
Mounting TypeDIN rail mounting
Rated Operational Voltage24 V DC
Rated CurrentUp to 820 A
Protection FunctionsOverload, short-circuit, phase failure, asymmetry, ground fault, motor stall
Operating Temperature Range-25°C to +60°C
Communication ProtocolsPROFIBUS DP, PROFINET, Modbus RTU
Analog OutputsUp to 2
Temperature MonitoringPTC/KTY, RTD (PT100/PT1000)
Digital OutputsRelay outputs, Solid-state outputs
Analog Inputs0/4-20mA, PT100/PT1000

Related product manuals