5
05.01
5.5 ”ANA module” control board
5-146
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
External 26.5 V infeed, enable, BERO inputs
S X431: Axis 1
S X432: Axis 2
Table 5-26 Connector X431; 8–pin Phoenix Combicon connector
Pin
X431 Type
1)
Function Typ. voltage/
limit values
1 M I Electronic ground
2 PV1 O P24EXT switched, axis 1 Max. 2.0 A
3 MV1 O M24EXT switched, axis 1
4 C1 Reserved, do not use
5 P24 I Input for external +24 V 26.5 V "2%
6 M24 I Input for external 0 V
7 663 I Module–specific enable signal 21 V...30 V
8 9 O Enable voltage, internal, +24 V
1) I = Input, O = Output
Table 5-27 Connector X432; 8–pin Phoenix Combicon connector
Pin X432 Type
1)
Function Typ. voltage/
limit values
1 M I Electronic ground
2 PV2 O P24EXT switched, axis 2 Max. 2.0 A
3 MV2 O M24EXT switched, axis 2
4 C2 Reserved, do not use
5 B1 I BERO input, axis 1 13 V...30 V
6 19 O Internal enable voltage, ground, term.19
7 B2 I BERO input, axis 2 13 V...30 V
8 9 O Enable voltage, internal, +24 V
1) I = Input, O = Output
Notice
A connection (jumper) between X431.6 and X432.3 is not permissible!
Max. terminal cross–section 2.5 mm
2
.
It is only necessary to supply terminals X431 pins 5 and 6 with 24 V if the 24 V
outputs of connectors X111/112, X121/122 or X431/432 are to be used.