5.3 ”SIMODRIVE 611 universal E HRS” control board
5-126
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
5.3.2 Description of the terminals and interfaces
The board–specific terminals and interfaces are available, common for both
drive A and B.
Table 5-14 Overview of the board–specific terminals and interfaces
Terminal Function Type
Technical specifications
No. Designa-
tion
1)
Signaling terminal, start inhibit (X421)
AS1
3)
Signaling contact
Start inhibit
NC Connector type: 2–pin conn. strip
Max. cond. cross–sect.: 2.5 mm
2
Contact: Floating NC contact
AS2
3)
X421
Feedback signal from
terminal 663
ontact:
oat
ng
contact
Contact load capability: at 250 V
AC
max. 1 A
4)
at 30 V
DC
max. 2 A
Relay, safe
start inhibit
AS2
AS1
T. 663
AS2
AS1
T. 663
Pulses not enabled (T. 663)
The gating pulses of the power
transistors are inhibited.
Pulses enabled (T. 663)
The gating pulses of the power
transistors are enabled.
Relay, safe
start inhibit
Terminals for supply and pulse enable (X431)
X431
Connector type: 5–pin conn. strip
Max. conductor cross–section: 1.5 mm
2
P24 X431.1 External supply for digi-
tal outputs
(+24 V)
S Voltage tolerance (including ripple): 10 V to 30 V
Max. aggregate current: 2.4 A
Note:
S The external supply is required for the four digital outputs
(O0 A O1 A and O0 B O1 B)
M24 X431.2 Reference for the ex-
ternal supply
S
.
,
.
an
.
,
.
.
S When dimensioning the external power supply, the total
current of all of the digital outputs must be taken into ac-
count.
9 X431.3 Enable voltage
(+24 V)
S Reference: Terminal 19
Maximum current(for the total group): Max. 500 mA
Note:
The enable voltage (terminal 9) can be used to supply the
enable signals (e.g. pulse enable) as 24 V auxiliary voltage.
Board–
specific terminals
and interfaces
5 Control Units 02.0305.08