6
05.01
6.3 Technical data
6-165
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
6.3.3 Technical data of the supplementary components
Components Order
number
Supply
voltage
Supply
current
Observe
the rotating
field!
Degree
of
protec-
tion
Weight
[kg]
Built–on fan for internal and ex-
ternal cooling
6SN11 62–
0BA02–0AAV
3–ph.
360..510 V
AC
45...65 Hz
0.2...0.3 A For the di-
rection of
rotation, re-
fer to the di-
rection of
the arrow
on the fan
IP 44 4
Hose cooling package 1 for an
individual module comprising:
S 2x module connection
flange, 2000 mm hose
S 1x cabinet connection flange
S 1x radial fan with cabinet
connection flange
1)
(refer to Fig. 2-7)
6SN11 62–
0BA03–0AA1
3–ph.
360..457 V
AC
47.5...62.5 Hz
1.0...1.2 A Counter–
clockwise
direction of
rotation
when view-
ing the
rotor
IP 54 8
Hose cooling package 2 for a
2–tier configuration of
I/R 55 kW and LT 200 A:
S 4x module connection
flange, 2000 mm hose
S 1x cabinet connection flange
S 1x radial fan with cabinet
connection flange
1)
(refer to Fig. 2-7)
6SN11 62–
0BA03–0CA1
3–ph.
360..457 V
AC
47.5...62.5 Hz
1.0...1.2 A Counter–
clockwise
direction of
rotation
when view-
ing the
rotor
IP 54 8
Motor circuit–breaker Size S00:
Setting value, 0.3 A
Setting value, 1 A
Size S0
Setting value, 0.3 A
Setting value, 1 A
3RV1011–0DA10 0.22–0.32 A
3RV1011–0KA10 0.9–1.25 A
3RV1021–0DA10 0.22–0.32 A
3RV1011–0KA10 0.9–1.25 A
Air baffle plate
width 100 mm
6SN1162–
0BA01–0AA0
If heat sensitive parts are located above the UI and/or PR module
with a clearance < 500 mm, e.g. cable ducts, then an air baffle plate
must be used
(refer to Chapter 12, Dimension drawings).
1)
Replacement filter element: Order No. AFF0
Can be ordered from: Pfannenberg GmbH
Postfach 80747
D–21007 Hamburg
!
Warning
The fan may only be commissioned if it is electrically connected to the module
housing (PE fan via module housing).
!
Caution
If the fan has the incorrect direction of rotation (refer to the arrow on the fan)
then cooling is not guaranteed!
Cooling
components
6 Infeed Modules11.0510.04