7.3 Line supply fuses, transformers and main switch
7-216
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
7.3.3 Assigning isolating transformers to the I/R modules
Table 7-8 Matching transformers with separate windings for 50 Hz/60 Hz line supplies
I/RF module
16 kW
I/RF module
36 kW
I/RF module
55 kW
I/RF module
80 kW
I/RF module
120
kW
Nominal rated power [kVA] 21 47 70 104 155
Power loss, max. [W] 650 1200 2020 2650 3050
Vector group YYn0 neutral point N can only be loaded with maximum 10%!
Short–circuit voltage uk [%] 3
Degree of protection acc. to
DIN EN 60529 (IEC 60529)
Degree of protection IP 00: ––> Order No. 0
Degree of protection IP 20: ––> Order No. 8
Degree of protection IP 23: ––> Order No. 2
1)
Humidity classification in
accordance with
DIN EN 60721–3–3
Class 3K5 condensation and formation of ice excluded
Permiss. ambient temperature
Operation C
Storage/transport C
–25 to +40, for power derating up to +55
–25 to +80
Approx. weight for
Degree of prot. IP 00 [kg]
Degree of prot. IP 20/23[kg]
120
131
200
216
300
364
425
536
600
688
Dim. (L x W x H) approx.[mm] 480 x 209 x
420
480 x 267 x
420
630 x 328 x
585
780 x 345 x
665
780 x 391 x 665
Max. conn., secondary
[mm
2
]
16 35 70 Cable lug according to
DIN 46235
Input voltage, 3–ph. 575 V – 500 V – 480 V AC 10%; 50 Hz – 10% to 60 Hz + 10%
Rated input current [A] 26 58 87 127 189
Max. conn., primary
[mm
2
]
16 35 50 70 Cable lug
according to
DIN 46235
Order No.
according to Catalog PD10
4BU43 95–
0SA7–0C
4BU47 95–
0SC3–0C
4BU55 95–
0SA4–0C
4BU58 95–
0SA6–0C
4BU60 95–
0SA6–0C
Input voltage, 3–ph. 440 V – 415 V – 400 V AC 10%; 50 Hz – 10% to 60 Hz + 10%
Rated input current [A] 31 69.5 104 154 228
Max. conn., primary
[mm
2
]
16 35 70 70 Cable lug
according to
DIN 46235
Order No.
according to Catalog PD10
4BU43 95–
0SA8–0C
4BU47 95–
0SC4–0C
4BU55 95–
0SA5–0C
4BU58 95–
0SA7–0C
4BU60 95–
0SA7–0C
Input voltage, 3–ph. 240 V – 220 V – 200 V AC 10%; 50 Hz – 10% to 60 Hz + 10%
Rated input current [A] 62 138.5 210 309 450
Max. conn., primary
[mm
2
]
35 70 Cable lug according to DIN 46235
Order No.
according to Catalog PD10
4BU43 95–
0SB0–0C
4BU47 95–
0SC5–0C
4BU55 95–
0SA6–0C
4BU58 95–
0SA8–0C
4BU60 95–
0SA8–0C
1)
For degree of protection IP 23, a 10% power derating must be taken into account
In conformance with the Standards with regulation: EN61558/VDE0532
Insulation Class: T40/b–H
7 Line Su
pp
l
y