EasyManua.ls Logo

Siemens SIMODRIVE 611 digital - Page 215

Siemens SIMODRIVE 611 digital
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
05.01
7.3 Line supply fuses, transformers and main switch
7-215
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
Table 7-7 Autotransformer for a 220 V input voltage, continued
I/RF module
120/156 kW
I/RF module
80/104 kW
I/RF module
55/71 kW
I/RF module
36/47 kW
I/RF module
16/21 kW
Max. dimensions
Drilling template in mm
Footprint, view from the top
t3
b4
t4
t1
t2
b3
b2
b1
t3
t1
t2
b
3
b2
b1
d
1
t1 = 370/460
t2 = 317
t3 = 53
t4 = 10
b1 = 220/465
b2 = 179
b3 = 41
b4 = 18
Height 330/555
t1 = 480/565
t2 = 418
t3 = 62
t4 = 15
b1 = 230/460
b2 = 205
b3 = 50
b4 = 22
Height 430/520
t1 = 480/565
t2 = 418
t3 = 62
t4 = 15
b1 = 300/460
b2 = 241
b3 = 59
b4 = 22
Height 430/520
t1 = 530/900
t2 = 470
t3 = 60
b1 = 290/600
b2 = 254
b3 = 71
d1 = 12.5
Height 520/720
t1 = 590/900
t2 = 530
t3 = 60
b1 = 320/600
b2 = 279
b3 = 81
d1 = 15
Height 585/720
1) Not IP20
2) 10% power derating required
3) FL = flat termination, hole 9 mm
The permissible current of the transformers, reactors etc. depends on the ambi-
ent temperature and the installation altitude. The permissible current/power rat-
ing of transformers and reactors is as follows:
I
n
(PD) reduced = cI
n
(PD)
1.1
0.9
0.7
40 50
C
m above sea level
1000 2000
c
a)
b)
a) The ambient temperature from +40 C
b) The installation altitude from 1000 m
Reduction factor c
as a function of:
30
Fig. 7-8 Reduction factor (derating) c
Operating
conditions
for all transformers
7 Line Su
pp
l
y
Connection10.04
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Related product manuals