To Previous Page IconTo Previous Page
Loading...
8
05.01
8.15 Examples of correctly and incorrectly connecting NE
8-317
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
8.15.2 Six–conductor connection to the line supply
Note
All X181 connections of a drive group must be electrically switched in
parallel!
All of the jumpers at X181 must be removed!
A maximum of four monitoring modules may be connected at X181 of an
NE module.
If a DC link is buffered (DC link connection), the voltage must always be
taken from between the reactor (L
K
) and the line supply infeed (NE).
Different line supplies may be used, e.g. using UPS.
For all of the following examples, cables must be routed so that they are
short–circuit and ground–fault proof (or fuse)!
e.g. NCU PMxx
P600
M600
U1 V1 W1 PE
PMxx PMxx
X181
M500
P500
2U1
1U1
2V1
1V1
2W1
1W1
X181
M500
P500
2U1
1U1
2V1
1V1
2W1
1W1
Correct!
1L1
L
K
1)
F
N
(X A)
Filter (X kW)
PE
1L2
1L3
Schematic diagram
2L1
F
N
(T10 A)
Filter (5 kW)
2L2
2L3
Six–conductor connection
to the line supply
Note:
1) L
k
for 5 kW and 10 kW integrated, therefore not necessary here!
2) DC link connection not permissible for six–conductor connection to the line supply!
NE
2)
MM
Twisted
cable
4 MM
Fig. 8-35 Examples for correct six–conductor connection to the line supply with a maximum of four monitoring modules
connected to a line infeed module (NE module)
8 Im
p
ortant Circuit Information05.08