6
05.01
6.4 HFD reactor
6-170
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
U/L1/C/L+
HFD reactor
Order No., refer to Table 6-9
HFD reactor, terminal connection
1)
PE 3 2 1
Cable connection to the resistor.
The cable length of 5 m may be
decreased but not increased.
ÏÏ
ÏÏ
Shield contact
gn/ye
PE
W/L3/D/L–
ÏÏÏÏ
ÏÏÏÏ
ÏÏÏÏ
ÏÏÏÏ
V/L2
bk
bk
bk
Schematic diagram
HFD resistor
Order No.
e.g.
6SL3100–1BE21–3AA0
Connecting the cable
to the HFD reactor
1) Jumper, 2–3–PE for potential connection (EMC) is provided as standard
1
2
3
PE
1)
Resistance
U/L1/C/L+
V/L2
W/L3/D/L–
PE
Resistor connection circuit to an HFD reactor
Note:
It is not permissible to route cables in or close to the warm airflow of the
damping resistor!
Mounting position:
Arbitrary mounting position but consider the
heat dissipation, if necessary, provide a ”Hot
surface” warning notice!
Fig. 6-11 Wiring, HFD reactor and damping resistor
6 Infeed Modules 11.0505.08
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182