7.1 Line supply connection conditions for line supply infeed
7-196
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
Table 7-1 Engineering information, if you dimension and select the transformer
yourself
Used
I/R module
P
n
/P^
Required rated power Sn of the
isolating/autotransformer
Required uk short–
circuit voltage
16/21 kW Sn 21 kVA uk 3%
36/47 kW Sn 46 kVA uk 3%
55/71 kW Sn 70 kVA uk 3%
80/120 kW Sn 102 kVA uk 3%
120/156 kW Sn 153 kVA uk 3%
UI module
used
P
n
/P^
Required rated power Sn of the
isolating/autotransformer
Required uk short–
circuit voltage
5/10 kW Sn 6.4 kVA uk 10%
10/25 kW Sn 13 kVA uk 10%
28/50 kW Sn 36 kVA uk 10%