EasyManua.ls Logo

Siemens SIMODRIVE 611 digital - Page 204

Siemens SIMODRIVE 611 digital
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
05.01
7.2 Voltage matching
7-204
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) -- 05/2008 Edition
A SIMODRIVE NE module and other loads/machines are connected at the
matching transformer (refer to Fig. 7-6).
Line fuses
PE
NE module
Line supply
connection/
transformer for
the plant
S
K
plant
Additional loads/
machines
V1U1 W1
S
K
line
Commutating
reactor
S
K
transformer
Matching trans-
former for the
machine
Line filter
For isolating
transformer:
Ground the star
point!
1)
Line fuses
1) Loadability, note dependent of the vector group!
Fig. 7-6 Connection schematic, matching transformer for additional loads
A matching transformer must be dimensioned for the total of all loads connected
to it. The apparent power required for the NE modules must be determined and
added as shown in Chapter 6.3.1, Table 6-6. If the transformer S
n
or S
K
is too
small, this can lead to increased line voltage dips and faults in the system and
in other loads at this connecting point.
!
Warning
A sufficiently high system fault level (short--circuit power) is required to ensure
that when a ground fault does occur, the fuses rupture in the specified time. An
insufficient system fault level (short--c ircuit power) increases the time to trip
beyond permissible levels (e.g. a fire is possible).
Matching
transformer
configuration
7L
ne Su
p
p
l
y
Connec
t
on 05.08
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Related product manuals