8.2 Infeed modules
8-241
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
The NE and monitoring modules have the following display elements (LEDs):
2 LED red – 5 V voltage level faulted
3 LED green – external enable signals not present (terminal 63 and/or terminal 64
missing)
4 LED yellow – DC link charged (normal operation)
5 LED red – line supply fault (single or multi–phase power failure at terminals
U1, V1, W1)
1)
– commutating reactor not available, incorrectly installed
or incorrectly selected
– system fault level of the line supply or transformer too low
6 LED red – DC link overvoltage
possible causes: Regenerative feedback off, setting–up operation,
line fault, for UI, PW either not operational or too small,
line supply voltage too high, dynamic overload, line filter
inserted between I/R and the commutating reactor
12
34
56
1 LED red – electronics power supply 15 V faulted
Note:
1) Detection time for line–supply failure, approx. 30 ms
Line–supply failure is detected from a 3-phase voltage < 280 V.
For a 1-phase line–supply failure, a pulse cancellation is initiated for the drive axes
after approx. 1 min. (stored signal). This is valid for
order number 6SN1114–10–01
Fig. 8-3 Display element, NE and monitoring module
Effects of the display states:
1 LED red bright: Pulses are cancelled for the complete drive group
2 LED red bright: Pulses are cancelled for the complete drive group
4 LED yellow dark: Pulses are cancelled for the complete drive group
5 LED red bright: Pulses are only cancelled for the I/R module (regenerative
feedback into the line supply no longer possible.
Axes initially continue to run. Ready relay drops out)
6 LED red bright: Pulses are cancelled for the complete drive group
Display elements
(LEDs)