EasyManua.ls Logo

Siemens SINAMICS GM150 - Page 104

Siemens SINAMICS GM150
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
In order to avoid additional locations where interference can be coupled in, long cables
should be shortened or routed where there is little interference.
If conductors or cables conduct signals of different classes, then the conductors and cables
must cross at a right angle. This especially involves sensitive and noisy signals.
Class 1:
Unshielded cables for ≤ 60 V DC
Unshielded cables for ≤ 25 V AC
Shielded analog signal cables
Shielded bus and data cables
Operator panel interfaces, incremental/absolute encoder cables
Class 2:
Unshielded cables for > 60 V DC and ≤ 230 V DC
Unshielded cables for > 25 V AC and ≤ 230 V AC
Class 3:
Unshielded cables for > 230 V AC/V DC and ≤ 1000 V AC/DC
Class 4:
Unshielded cables for > 1000 V AC/DC
Shield connection
Do not use cable shields to conduct current. In other words, cable shields must not
simultaneously act as neutral or PE conductors.
Apply the cable shield so that it covers the greatest possible surface area. Use ground
clamps, ground terminals or ground screw connections.
Avoid extending the cable shield to the grounding point using a wire. This reduces the shield
effectiveness by up to 90%.
Electrical connection
6.2 Electromagnetic compatibility
SINAMICS GM150 6SL3815-2LN41-4AA2
104 Operating Instructions 04/2017

Table of Contents

Other manuals for Siemens SINAMICS GM150

Related product manuals