LEDs of the DM10 diagnostics module
The LEDS installed on the diagnosis module indicate the logic state of the signals present
between the communication partners of the DM10 diagnosis module.
Table 8-10 LEDs of the DM10 diagnostics module
LED Communication partner Meaning: signal 1 / signal 0
H30 -X232/-X32 Control signals from PSA present / not present
H31 -X232/-X32 Control signals from PSA present / not present
H32 -X232/-X32 Control signals from PSA present / not present
H33 -X232/-X32 Control signals from PSA present / not present
H34 -X33/-X5 Binary plant signals for diagnosis on PADU8 present / not present
H35 -X33/-X5 Binary plant signals for diagnosis on PADU8 present / not present
H36 -X33/-X5 Binary plant signals for diagnosis on PADU8 present / not present
H37 -X33/-X5 Binary plant signals for diagnosis on PADU8 present / not present
H20 -X34/-X36 Internal power supply 1P24 OK / not OK
H21 -X34/-X36 Internal power supply 1N24 OK / not OK
H22 -X35/-X36 External power supply 2P24_1 and 2P24_2 OK / 2P24_1 or 2P24_2 not OK
H23 - Internal and external power supplies OK / not OK
8.5.3.3 Diagnostics via parameters
Diagnostic parameters for the device status
r0002 Drive status
Display of drive status
r0046 Missing enable signals
Display of the missing enable signals that are preventing the drive control from being commissioned
Bit Signal name 0-signal 1-signal
00 OFF1 enable missing No Yes
01 OFF2 enable missing No Yes
02 OFF3 enable missing No Yes
03 Enable run missing No Yes
05 External power-on inhibit active No Yes
06 Commissioning not yet complete No Yes
09 Infeed enable missing No Yes
10 Ramp-function generator enable missing No Yes
11t No start ramp-function generator No Yes
12t No setpoint enable No Yes
16 OFF1 internal enable missing No Yes
17 OFF2 internal enable missing No Yes
Operation
8.5 Fault and system messages
SINAMICS GM150 6SL3815-2LN41-4AA2