Screw type Set screws and
headless screws
Head screws with
slit
Head screws with
hexagon profile
nm in - lb nm in - lb nm in - lb
M3.5 0.5 4.4 1.0 8.9 1.0 8.9
M4 0.8 7.1 1.3 11.5 1.3 11.5
M5 1.0 8.6 2.5 22.1 2.5 22.1
M6 1.3 11.5 3.0 26.6 3.5 31.0
M8 1.8 15.9 3.9 34.5 7.2 63.7
M10 - - 4.8 42.5 13 115
M12 - - - - 18 159.3
M16 - - - - 30 265.5
Observe the tightening torques of the terminal manufacturer and the test torques according to
DIN EN 60999-1, VED 609-1
Note
A different torque of 8 - 10 Nm is applicable for the M8 screw connection for the PowerCard.
Note
Replacing the current transformer
The current transformer may only be replaced by technicians trained by Siemens.
Note
Defective door interlock system
Contact Customer Support if the door interlock system becomes defective.
See also
Service & Support (Page 231)
9.7.2 Replacing the diode module
The Basic Line Module comprises several diode modules. The diode module is a replaceable
unit. A diode module weighs 13 kg. It takes experienced personnel 20 minutes to replace the
diode rectifier.
Required tools
10 mm open-ended wrench or socket wrench
13 mm open-ended wrench or socket wrench
Torque wrench
Maintenance
9.7 Repairs
SINAMICS GM150 6SL3815-2LN41-4AA2