Removing a defective diode module
1. Remove the screw connection between the line supply connection busbar and the
connection strap for the diode.
2. Release the screw connection of the PowerCard with the mounting bracket.
Note
The mounting bracket is not part of the diode module and must remain on the device.
Figure 9-8 Release the screw connection of the line supply connection busbar
3. Remove the screwed connection between the DC-link busbars and the heat sinks.
Figure 9-9 Release the screw connection of the DC link busbar
Maintenance
9.7 Repairs
SINAMICS GM150 6SL3815-2LN41-4AA2
212 Operating Instructions 04/2017