Table 7-1 PROFIBUS interface X126
Pin Signal name Meaning Range
1 - Not assigned
2 M24_SERV Power supply for teleservice, ground 0 V
3 RxD/TxD–P Receive/transmit data P (B) RS485
4 CNTR–P Control signal TTL
5 DGND PROFIBUS data reference potential
6 VP Supply voltage plus 5 V +- 10%
7 P24_SERV Power supply for teleservice, +24 V 24 V (20.4 V to 28.8
V)
8 RxD/TxD–N Receive/transmit data N (A) RS485
9 - Not assigned
NOTICE
Damage to components
If CAN cables are connected to the X126 interface, the CU320 or other CAN bus nodes can
be damaged.
Do not connect any CAN cables to the X126 interface.
Note
A teleservice adapter can be connected to the PROFIBUS interface X126 for remote
diagnostics purposes.
The power supply for the teleservice (terminals 2 and 7) can have a load of up to 150 mA.
Diagnostics LED
The meaning is explained in the table below.
Table 7-2 Description of the DP1 LEDs
Color Status Description
----- Off Cyclic communication has not (yet) taken place.
Note:
If the Control Unit is operational, the PROFIdrive is ready for communication. The DP1
LED illuminates.
Green Continuous light PROFIBUS is ready for communication and cyclic communication is taking place.
Green 0.5 Hz flashing light Full cyclic communication is not yet taking place.
The controller is not transferring any setpoints.
During isochronous operation, no or a faulty global control (GC) is transferred by the
controller.
Red Continuous light Cyclic communication has been interrupted.
Start-up
7.2 Description and configuration of the PROFIBUS interface
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017 121