8.2.3.5 Commissioning / service drive commissioning
Commissioning / service / drive commissioning menu structure
&RPPLVVLRQLQJ
VHUYLFH
'ULYH
FRPPLVVLRQLQJ
%DVLF
FRPPLVVLRQLQJ
&RPSOHWH
FRPPLVVLRQLQJ
0RWRU
LGHQWLILFDWLRQ
5HVHWIDQ
RSHUDWLQJWLPH
0DLQPHQX
Figure 8-11 Commissioning / service / drive commissioning menu structure
1. Press the <Menu>. key
2. Press the <▼> function key to select the "Commissioning/Service" row. Press the <OK>
function key to confirm the selection.
3. Press the <▼> function key to select the "Device commissioning" row. Press the <OK>
function key to confirm the selection.
4. Press the <▼> function key to select the desired menu item.
Basic commissioning
In this menu, you can set the following parameters for the basic parameterization:
Table 8-4 Drive Object VectorMV
Parameter Parameter text
p700[0] Macro binector input (BI)
p1000[0] Macro connector inputs (CI) for speed setpoints
p1070[0] CI: Main setpoint
p1080[0] Minimum speed
p1082[0] Maximum speed
p1120[0] Ramp-function generator ramp-up time
p1121[0] Ramp-function generator ramp-down time
p1135[0] OFF3 ramp-down time
Complete commissioning
In this menu, all of the parameters of the basic parameterization except for the parameters of
the DO B_Infeed can be set.
Operation
8.2 Operation via the AOP30 operator panel
SINAMICS GM150 6SL3815-2LN41-4AA2
152 Operating Instructions 04/2017