Table B-11 Terminal assignment of customer interface TM31
Terminal module Connec‐
tor
Terminal Internal control
.HC-A31 -X521 1,2 AI p4052.0 p1070 Main speed setpoint
3,4 AI p4052.1 p1075 Supplementary speed setpoint
1,2 AO p4071.0 r0063 Actual speed value
4,5 AO p4071.1 Supplementary actual speed value
B.2.2 Terminal assignment of the NAMUR terminal strip (option B00)
The NAMUR terminal strip is a standard terminal strip defined for the chemicals/
pharmaceutical industry. It is defined as follows:
Table B-12 Terminal assignment of NAMUR terminal strip
Terminal No. Designation Preassignment Comments
-A1-X2 1
1.0
1.1
M Reference conductor to 24 VDC
supply
3 terminals
3
3.0
3.1
P24 24 VDC supply Protected internally with fuse (2 A)
3 terminals
10 DI ON command drive
11 DI OFF (dynamic) See .HC -A31 -X520:3.
12 DI Faster ≙ MOP raise
13 DI Slower ≙ MOP lower
14 DI RESET ≙ Acknowledge faults
15 DI Lock ≙ OFF3
16 DI Counterclockwise "0" signal for CW phase sequence
"1" signal for CCW phase sequence
≙ direction of rotation changeover
17, 18 Power disconnection External safety circuit
Circuit-breaker no OFF command
30, 31 Ready for operation Relay output (NO contact)
32, 33 Operation; motor turning Relay output (NO contact)
34 DO (COM) Fault Relay output (two-way contact)
35 DO (NO)
36 DO (NC)
50, 51 AI 0/4 mA to 20 mA Speed setpoint
60, 61 AO 0/4 mA to
20 mA
Main actual speed value
62, 63 AO 0/4 mA to
20 mA
Motor current Defaulted with motor current – can be repara‐
meterized for other variables.
Technical data and drawings
B.2 Terminal assignments
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017 239