6.5.2 Preparations for connecting the power cables
Disconnect the cabinets from the power supply.
Ensure that all the necessary safety measures have been taken at the installation location.
Allow unimpeded access to the cable clamping bar in the cabinets.
6.5.3 Connecting power cables
Note
The screws and accessories are not included in the scope of delivery.
Contact surface
Cable clamp
Figure 6-4 Example: Connecting the power cables
1. Clean the contact surfaces immediately before screwing the connections. Use spirit and
a lintless cloth for cleaning.
2. Apply a thin film of grease. Electrolube 2G is a suitable lubricator.
3. Screw the cable lug with a M12 screw and, if necessary, with a washer to the contact
surface. Tighten the nut (torque: 50 Nm).
4. Remove the cable shield. Fasten the cable with cable clamps to the cable support trail.
Electrical connection
6.5 Connection
SINAMICS GM150 6SL3815-2LN41-4AA2