Mechanical ambient conditions
Table B-6 Mechanical ambient conditions
Storage with suitable packag‐
ing
Transport with suitable pack‐
aging
Operation
Class 1M2 according to
DIN EN 60721‑3‑1
(IEC 60721‑3‑1)
2M2 according to
DIN EN 60721‑3‑2
(IEC 60721‑3‑2)
3M1 according to
DIN EN 60721‑3‑3
(IEC 60721‑3‑3)
Other ambient conditions
Table B-7 Other ambient conditions
Storage with suitable packag‐
ing
Transport with suitable pack‐
aging
Operation
Biological ambient conditions
according to class
1B1 according to DIN EN
60721‑3‑1 (IEC 60721‑3‑1)
2B1 according to DIN EN
60721‑3‑2 (IEC 60721‑3‑2)
3B1 according to DIN EN
60721‑3‑3 (IEC 60721‑3‑3)
(without harmful flora)
Chemically active substan‐
ces according to class
1C1 according to DIN EN
60721‑3‑1 (IEC 60721‑3‑1)
2C1 according to DIN EN
60721‑3‑2 (IEC 60721‑3‑2)
3C1 according to DIN EN
60721‑3‑3 (IEC 60721‑3‑3)
Mechanically active substan‐
ces according to class
1S1 according to DIN EN
60721‑3‑1 (IEC 60721‑3‑1)
2S1 according to DIN EN
60721‑3‑2 (IEC 60721‑3‑2)
3S1 according to DIN EN
60721‑3‑3 (IEC 60721‑3‑3)
B.1.6 Technical specifications of the common power supply
Table B-8 Technical specifications of the common power supply
Rated voltage U
Erated
/ rated input frequency f
Erated:
1-phase 115 VAC / 60 Hz
1-phase 230 VAC / 50 Hz / 60 Hz
1-phase 240 VAC / 50 Hz / 60 Hz
Peak value of the rated output voltage U
Arated
: 55 V ±3%
Rate of rise of voltage (dv
a
/dt)
max
: 2 kV/μs
Rated output frequency f
Arated
: 100 kHz ±5%
Natural convection
,
T
Env
= 55° C, P
A1Rated
: 87.5 W for UE
RATED
=
230 V
75 W for UE
RATED
= 115 V
Rated total power output with natural convection
,
T
Env
= 55° C,
P
A1Rated
:
350 W for UE
RATED
= 230 V 300 W for UE
RATED
=
115 V
Possible load duty cycle Transient, 60 s - 1.2 x P
ARated
Recovery time 30 minutes
Mean value of output current per half-period per output, I
ARated
: 1.25 A
Peak value of output current during rated operation per output, I
Amax
: Approx. 6.5 A
Switch-off overcurrent limit value per output, I
Aoff
: 10 A
Efficiency under rated conditions η > 80%