Connecting the motor to the dv/dt filter
Figure 3-11 Connecting the motor to the dv/dt filter
Restrictions when using the dv/dt filter
The drive may be operated only with following maximum currents:
4 kA drive: 1680 A (without filter 1750 A)
5 kA drive: 1780 A (without filter 1850 A)
The pulse frequency of the drive must not exceed 200 Hz.
The permissible output frequency of the drive must not exceed 100 Hz.
The following line length between the filter output and the motor is permitted with shielded
cables (cable cross-section 185 mm
2
):
200 m when six parallel cables are used
400 m when three parallel cables are used
The re-cooling unit requires 10 liter more flow
Description
3.6 Description of options
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017 61