Par. No. Name Range  Default Unit
P0610 Motor I
2
t reaction 0 - 2 1 --
Defines reaction when motor I
2
t reaches warning threshold.
Possible settings:
0 Warning, no reaction, no trip
1 Warning, Imax reduction, trip F0011
2 Warning, no reaction, trip F0011
Dependency: 
See parameter P0611.
Note: 
Default value depends on connection macro selected. See Table 7-11 for details
P0611 Motor I
2
t time constant 0 - 16000 Depends on 
inverter type
s
Thermal time constant for the motor. 
Dependency:
P0611 < 99 s: I
2
T-calculation inactive
To activate I
2
T calculation, set P0611 to a value > 99 s. 
Note: 
The value of P0611 is estimated according to the motor data during quick commissioning. When the 
calculation of motor parameters during quick commissioning is complete, the stored value can be replaced 
by the value given by the motor manufacturer. 
P0640 Motor overload factor [%] 10.0 - 400.0 110.0 %
Defines motor overload current limit in [%] relative to P0305 (rated motor current).
P0701 Function of digital input 1 0 - 99 0 --
Selects function of digital input 1.
Possible settings:
0 Digital input disabled
1 ON/OFF 1
2 ON reverse/OFF1
3 OFF2 - coast to standstill
4 OFF3 - quick ramp down 
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (direct selection)
16 Fixed setpoint (direct selection + ON)
99 Enable value 722.0 set in other parameters.
Note: 
Default value depends on connection macro selected. See Table 7-11 for details
Parameter list
SINAMICS V10
84 Operating Instructions, 08/2011, A5E03453178 (this is not an order number)