Par. No. Name Range Default Unit
P0702 Function of digital input 2 0 - 99 0 --
Selects function of digital inputs 2.
Possible settings:
Same as the settings of P0701 except value 99.
P0702 = 99 : Enable value 722.1 set in other parameters.
Note:
Default value depends on connection macro selected. See Table 7-11 for details
P0703 Function of digital input 3 0 - 99 0 --
Select function of digital input 3.
Possible settings:
Same as the settings of P0701 except value 99.
P0703 = 99 : Enable value 722.2 set in other parameters..
Note:
Default value depends on connection macro selected. See Table 7-11 for details
r0722 Binary input values -- -- --
Displays status of digital inputs.
Bitfields:
Bit00 Digital input 1 0 OFF 1 ON
Bit01 Digital input 2 0 OFF 1 ON
Bit02 Digital input 3 0 OFF 1 ON
Note:
Segment is lit when signal is active
The 7-segment display of the bit-parameters (binary parameters) is explained in Fig. 6-12 of Section 6.3.2.
P0725 PNP/NPN digital inputs 0 - 1 1 --
Switches between active high (PNP) and active low (NPN). This is valid inputs for all digital inputs
simultaneously.
The following is valid by using the internal supply:
Possible settings:
0 NPN ⇒ low active
1 PNP ⇒ high active
Value:
NPN: terminals 7/8/9 can be connected via terminal 6 (0V)
PNP: terminals 7/8/9 can be connected via terminal 5 (24V)
Parameter list
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number) 85