EasyManua.ls Logo

Siemens SIRIUS 3SK1

Siemens SIRIUS 3SK1
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.2 Explanation of the device's functions
Explanation of the device functions (DIP switches)
DIP
switch
Parameter Function
1 Start type
Autostart: The safety-related outputs are switched to the active position as soon as the
switch-on condition is satis󹪝ed at the sensor inputs IN1, IN2, INF and INK. The START button
connecting terminal INS is not queried.
Monitored start: The safety-related outputs are switched to the active position as soon as
the switch-on condition is met at the IN1, IN2, INF and INK sensor inputs and the START
button at the INS terminal is actuated (start with the falling edge).
2 Cross-circuit de‐
tection
Cross-circuit detection is only possible with 󹪞oating sensors. The sensors must be connected
between T1 - IN1 and T2 IN2. At the terminals IN1 and PAR (if used), the test signal of terminal
T1 is expected; at the terminals IN2 and INF , the test signal of T2 is expected. The device detects
a sensor fault if the signal at the terminals IN1, PAR or IN2, INF does not match the test signals
T1, T2.
Cross-circuit detection must be deactivated if electronic sensors such as light arrays or laser
scanners are connected. The 3SK1 now no longer monitors the sensor inputs for cross-circuit
detection. Usually, the outputs of safety sensors (OSSD) are already monitored for cross-circuits
in the sensor.
Devices with PAR terminals expect the test signal T2 at the parameterization input. A 24 V signal
at the PAR or INF terminals results in a fault (cross-circuit at the input).
3 Type of connec‐
tion
1 sensor with 2 contacts 1 x two-channel; NC/NC.
It is expected here that both contacts be open simultaneously.
With the additional connection of T1 to PAR, this DIP parameterization applies to ONE two-
channel sensor with NC/NO contacts.
2 sensors with one contact each 2 x single-channel; NC / NC.
In this case, both sensors are AND-connected. Simultaneity is not monitored.
4 Startup testing After a power failure, startup testing requires that the sensors at IN1 and IN2 are actuated once
by the system operator.
Con󹪝guration / operation
9.2 Explanation of the device's functions
SIRIUS 3SK1 Safety Relays and 3RQ1 Positively-Driven Coupling Relays
176 Equipment Manual, 05/2021, A5E02526190021A/RS-AE/005

Table of Contents

Other manuals for Siemens SIRIUS 3SK1

Related product manuals