Con󹪝guration / operation
9
9.1 Procedure for con󹪝guration
General information:
It is only possible to change the con󹪝guration (DIP switch, NC/NO evaluation, potentiometer,
input and output expansion) in con󹪝guration mode. Modi󹪝cations during operation are not
accepted.
A con󹪝guration change (DIP switch, NC/NO evaluation, potentiometer) is indicated in safety
mode by the "DEVICE" LED 󹪞ashing green/yellow, but does not change the device function.
In safety mode, if a change in the system con󹪝guration (input and output expansion) is
detected, the device switches to error mode ("DEVICE" LED and "SF" LED red). A restart is only
possible using Power OFF/ON.
Procedure for con󹪝guring a basic unit
1. Set the con󹪝guration (DIP, PAR, potentiometer, input expansion, output expansion) in
accordance with the desired function.
2. Connect the power supply.
3. If the device detects a modi󹪝ed con󹪝guration, it remains in con󹪝guration mode (LEDs 󹪞ash)
during power up.
4. Con󹪝rm the new con󹪝guration by operating the SET/RESET pushbutton for more than 1s.
5. The con󹪝guration has been accepted and the device changes to safety mode.
Note
Con󹪝guration and setting the delay time
A change to the con󹪝guration must only ever be carried out when the system is disconnected
from the power.
In safety mode, an adjustment to the potentiometer does not result in a change to the
parameterized delay time.
A change to the potentiometer setting made during operation is not accepted and is indicated
in safety mode by a yellow/green 󹪞ashing "DEVICE" LED. The device can be restarted by
performing a RESET (pressing the SET/RESET button) or by disconnecting and reconnecting the
supply voltage. Following a restart, the device remains in safety con󹪝guration mode during
power up (all safety-related outputs are shut down) until the new delay time is accepted by
pressing the SET/RESET button.
SIRIUS 3SK1 Safety Relays and 3RQ1 Positively-Driven Coupling Relays
Equipment Manual, 05/2021, A5E02526190021A/RS-AE/005 175

Table of Contents

Other manuals for Siemens SIRIUS 3SK1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS 3SK1 and is the answer not in the manual?

Siemens SIRIUS 3SK1 Specifications

General IconGeneral
BrandSiemens
ModelSIRIUS 3SK1
CategoryRelays
LanguageEnglish

Related product manuals