EasyManuals Logo

Siemens SIROTEC Equipment Manual

Siemens SIROTEC
570 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #130 background imageLoading...
Page #130 background image
Line Connection Booksize
2.13 Line connection variants
Booksize power units
130 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
2.13.3.5 Assignment of autotransformers to Smart Line Modules
Table 2-46 Autotransformers for 480/440 V input voltage
Smart Line Module
5 kW /10 kW /16 kW 36 kW
Rated power [kVA]
Autotransformer IP00
21
46.5
Input voltage [V] 480/440 V AC 3-phase ± 10%; 50 Hz - 5% to 60 Hz + 5%
Output voltage [V] 400 V AC, 3-phase
Vector group Yna0
Permiss. ambient temperature
Operation [°C]
-25 to +40, for power de-rating up to +55 °C, ISOKL: H, t
a
= 40
Humidity rating in accordance with DIN
EN 60721-3-3
Cl. 3K5, Condensation and icing excluded
Low air temperature 0 °C (+32 °F)
Degree of protection to EN 60529
(IEC 60529) IP00
Degree of protection IP00: _ → Order No. A
Order No. 4AP2796-0EL40-2X_0 4AU3696-0ER20-2X_0
Power loss [W]
Autotransformer IP00
160
430
Short-circuit voltage uk [%] ≤ 1.5
Conn. cross-section, max.
primary/secondary sides
16 mm
2
35 mm
2
Fuse, primary side 35 A gL 80A gL
Weight [kg], approx. for
Degree of protection IP00
29
52
Terminal arrangement 1U1/1U3/1V1/1V3/1W1/1W3/2U1/2V1/2W1/N
1U1 to 1W1 = 480 V input, 1U3 to 1W3 = 440 V input,
2U1 to 2W1 = 400 V output, N = neutral point

Table of Contents

Other manuals for Siemens SIROTEC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIROTEC and is the answer not in the manual?

Siemens SIROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIROTEC
CategoryDC Drives
LanguageEnglish

Related product manuals