Line Modules Booksize
3.4 Basic Line Modules with internal air cooling
Booksize power units
224 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
NOTICE
The 24 V terminal adapter may only be withdrawn vertically to the front panel (i.e. not at an
angle)!
3.4.7 Technical data
Table 3-32 Technical data: Basic Line Modules
Internal air cooling 6SL3130- 1TE22-0AA0 1TE24-0AA0 1TE31-0AA0
Rated power kW 20 40 100
Infeed:
Rated power (S1)
1)
Infeed power (S6-40 %)
1)
Peak infeed power
1)
kW (Pn)
kW (Ps6)
kW (Pmax)
20
26
60
40
52
120
100
130
175
Braking power:
Continuous power
Peak power
kW (Pn)
kW (Pmax)
5
40
10
80
-
-
Line supply voltages:
Line voltage
Line frequency
Electronics power supply
V
ACrms
Hz
V
DC
380 V 3 AC – 10% (-15% < 1 min) up to 480 V 3 AC + 10%
2)
47 to 63
24 (20.4 – 28.8)
DC link voltage:
Overvoltage trip threshold
Undervoltage trip threshold
V
DC
V
DC
V
DC
480 – 720
820 ± 2 %
360 ± 2 %
Rated input current:
at 380 V
AC
at 480 V
AC
/528 V
AC
at 480 V; S6-40%)
Peak current (at 400 V
AC
/480 V
AC
)
A
AC
A
AC
A
AC
A
AC
34.5
31/29
38
113/91
69
62/58
78
208/172
172
154/145
193
265/252
DC link current (at 600 V
DC
):
Rated current
at S6-40%
Peak current
A
DC
A
DC
A
DC
33.5
43
100
67
87
200
167
217
292
DC link busbar current carrying
capacity
A
DC
100 100 200
24 V busbar current carrying capacity A
DC
20 20 20
Electronics current consumption A
DC
1 1.4 2.0
Total power loss
(including electronic losses)
3)
W 144 283.6 628
Max. ambient temperature
without derating
°C 40 40 40
Max. ambient temperature
with derating
°C 55 55 55
DC link capacitance μF 940 1880 4100