Engineering and remote access
3.6 Cyclic and acyclic data
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
107
Slot
Subslot
Data
Description
Data size
Battery change
recommended
Battery replacement recommend-
ed: Battery capacity is insufficient
to achieve the specified buffer
time:
0: no
255: yes
Unsigned8
Not used
-
Unsigned8
Battery charge level
Battery charge level in %:
0-100: 0-100%
255: unknown battery
Unsigned8
Battery connection
maintenance
from V2.1
Connection to the battery inter-
rupted: Check the connection and
fuse:
0: no maintenance required
255: maintenance required
Unsigned8
3.6.2 Reading and writing data sets
An overview of all data sets, which are communicated between the SITOP UPS1600 and the
PROFINET IO-Controller is provided in the following table. Here, a distinction is made
between the following data sets:
Reading data sets: Data that is sent from the SITOP UPS1600 to the
PROFINET IO-Controller.
Writing data sets: Data that is sent from the PROFINET IO-Controller to the SITOP
UPS1600.
Index Slot Sub-
slot
Data set Type Description Data size
0x0001
0
1
Buffering parameters
Reading/
writing
Buffer parameters.
14 bytes
16 bytes
(from V2.4)
0x0002
0
1
Battery parameters
Reading/
writing
Parameters of the connected battery
modules
5 bytes
0x0003
0
1
Charging parameters
Reading/
writing
Charge parameters of the connected
battery modules
4 bytes
0x0004
0
1
Reset parameters
Reading/
writing
Reset parameters.
1 byte
0x0005
0
1
Battery information
parameters
Reading
Information about the connected SITOP
BAT1600 or SITOP UPS1100 battery
modules. This information is available
via the link "Energy Storage".
1024 bytes
556 bytes
(from V2.4)
0x0006
0
1
Device information
Parameters
Reading
Information about the
SITOP UPS1600.
124 bytes
0x0007
0
1
Hardware settings
parameters
Reading
Hardware settings of the
SITOP UPS1600 (settings that were
made at the front of the device).
8 bytes