Engineering and remote access
3.6 Cyclic and acyclic data
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
107
recommended
Battery replacement recommend-
ed: Battery capacity is insufficient
to achieve the specified buffer
time:
• 0: no
Battery charge level in %:
• 0-100: 0-100%
maintenance
from V2.1
Connection to the battery inter-
rupted: Check the connection and
fuse:
• 0: no maintenance required
255: maintenance required
3.6.2 Reading and writing data sets
An overview of all data sets, which are communicated between the SITOP UPS1600 and the
PROFINET IO-Controller is provided in the following table. Here, a distinction is made
between the following data sets:
• Reading data sets: Data that is sent from the SITOP UPS1600 to the
PROFINET IO-Controller.
• Writing data sets: Data that is sent from the PROFINET IO-Controller to the SITOP
UPS1600.
Index Slot Sub-
Data set Type Description Data size
writing
16 bytes
Parameters of the connected battery
modules
Charge parameters of the connected
battery modules
parameters
Information about the connected SITOP
BAT1600 or SITOP UPS1100 battery
modules. This information is available
via the link "Energy Storage".
556 bytes
(from V2.4)
Device information
Parameters
Information about the
SITOP UPS1600.
parameters
SITOP UPS1600 (settings that were
made at the front of the device).